23
Gen Under Volt
24
Under Speed
25
Over Speed
26
Under Freq
27
Over Freq
28
High Temp.
29
Low OP
30
Low Fuel Level
31
Aux. Sensor
32
Loss of Speed Signal (0-20.0)s
33
Charge Alt Failure
34
Battery Over Volt
35
Battery Under Volt
36
Current Trans.
Full Load Current
37
Rating
Over Current Percen-
38
tage
HGM410N/HGM420N GENSET
CONTROLLER USER MANUAL
(30-620)V
184
(0-6000)r/min
1200
(0-6000)r/min
1710
(0-75.0)Hz
40.0
(0-75.0)Hz
57.0
(80-140)ºC
98
(0-400)kPa
103
(0-100)%
10
(80-140)ºC (0-400)kPa
98
(0-100)%
5.0
(0-30)V
6.0
(12-40)V
33.0
(4-30)V
8.0
(5-6000)/5
500
(5-6000)A
500
(50-130)%
120
When generator voltage has fallen below the set
value and the "Gen abnormal delay" has expired,
Gen Under Voltage is active. When set the value as
30V, the controller does not detect under voltage
signal.
When engine speed has fallen below the set value
for 10s, Under Speed is active. It will initiate a shut-
down alarm signal.
When engine speed has exceeded the set value for
2s, Over Speed is active. It will initiate a shutdown
alarm signal.
When generator frequency has fallen below the set
value but Not equal to 0 for 10s, Under Frequency
is active. It will initiate a shutdown alarm signal.
When generator frequency has exceeded the set
value for 2s, Over Frequency is active. It will initia-
te a shutdown alarm signal.
When the temperature value of the external
temperature sensor exceeds the set value, "High
Temperature" timer is initiated. Detecting only after
safety on delay has expired. If the set value is 140,
high temperature signal will not be sent (this only
concerns external temperature sensor, not high
temperature signal via config. input port).
When the external pressure sensor value falls
below this set value, "Low Oil Pressure" timer is
initiated. Detecting only after safety on delay has
expired. If the set value is 0, low oil pressure signal
will not be sent (this only concerns pressure sen-
sor and does not concern low oil pressure warning
signal via configurable input port)
When the liquid level of the external sensor falls
below the set value, "Low Fuel Level" timer is
initiated. (this only concerns fuel level sensor and
does not concern low fuel level warning signal via
configurable input port)
Each value correspond to above 28 (Temperature
sensor), 29 (Oil pressure sensor) and 30 (Level
sensor), respectively.
If the set value is 0, only warning and not to shut-
down the generator.
During generator is normal running, when alterna-
tor D+(WL) voltage has fallen below the set value
and remains for 5s, It will initiate a shutdown alarm
signal.
When battery voltage has exceeds the set value
and remains for 20s, It will initiate a warning alarm
signal. Only warning and not to shutdown the
generator.
When battery voltage has fallen below the set
value and remains for 20s, It will initiate a warning
alarm signal. Only warning and not to shutdown
the generator.
The ratio of external CT
Generator's rated current, used for load over cur-
rent calculating.
When the load current has exceeded the set value,
"over current" delay is initiated.