Descargar Imprimir esta página

Smartgen HGM410N Manual De Instrucciones página 12

Publicidad

Idiomas disponibles

Idiomas disponibles

5.PARAMETERS SETTINGS
Start the controller, then press
1. Set Parameters
2. Information
3. Language
4. Event Log
5. Maintenance Setting
a)Parameters Setting
a)Parameters Setting
"0318" can set all items in parameters during inputting password. When default password has been changed, it
needs to input the same password with controller for parameter setting via PC software. If more parameter items
need to be set or password is forgotten, such as voltage and current calibration, please contact with the factory.
Note1:
Note1:
1)HGM410N, there are not items 1-5 in parameters; programmable output 1-4 have no digital outputs about mains.
2)Please modify the parameters in standby mode (crank conditions, auxiliary input and output configuration, multi delays, etc.)
otherwise shutdown alarm or other abnormal conditions may appear.
3)The over-voltage threshold must be greater than the under-voltage threshold; otherwise over-voltage and under-voltage will
occur at the same time.
4)The over-speed threshold must be greater than under-speed threshold, otherwise over speed and under speed will occur at
the same time.
5)Set frequency value (after crank disconnect) as low as possible, in order to disconnect starter quickly.
6)Programmable input 1-4 cannot be set as the same items, otherwise it cannot realize correct function; programmable output
1-5 can be set as the same item.
7)Digital input 3 can be configured as Fuel Level Sensor. Digital input 4 can be configured as Temperature Sensor, Oil Pressure
Sensor and Water Level Sensor. Digital input and sensor need to be picked one: if input is chosen, the corresponding digital input
parameter is active and the sensor parameter inactive but saved; otherwise if sensor is chosen, the corresponding sensor para-
meter is active and the digital input parameter is inactive but saved.
8)If need to shut down after cooling, please set any input as " stop after cooling ", then connect this input to ground; or set high
temperature stop action as "cooling stop"
b)Information
b)Information
LCD will display some information of controller, such as software version, hardware version, issue date.
Note: Pressing
Note:
c)LCD contract
c)LCD contract
Press and
(or and ) can adjust LCD contract. Adjustment range is 0-7.
d)Language
d)Language
User may select display language as Chinese, English, Spanish, Russian, Turkey and French.
e)Event Log
e)Event Log
Users can check event log (max. 99) on this interface including start/stop info and shutdown alarms.
f)Maintenance Setting
f)Maintenance Setting
The default password (when enter maintenance setting) is 0 (it needs to contact sales or after sale personnel to
change the password). It'll refresh maintenance time after entered maintenance setting.
HGM410N/HGM420N GENSET
CONTROLLER USER MANUAL
to enter into the parameters setting menu as below:
will display the status of digital inputs and outputs.
12

Publicidad

loading

Productos relacionados para Smartgen HGM410N

Este manual también es adecuado para:

Hgm420n