OMNIA M 3.2
8.7 Application 7
The units are installed in parallel and can be used for cooling, heating and hot water.
6 units can be connected in parallel. Please refer to 9.7.5 for the parallel system electrical control system connection
diagram.
The parallel system can control and view the operation of the entire system only by connecting the master to the wire
controller;
If the DHW function is required, the water tank can only be connected to the master unit water circuit through a three-way
valve, and controlled by the master unit;
If you need to link with AHS, the AHS can only be connected to the master waterway and controlled by the master unit;
The connection and function of the terminal are the same as the single unit, please refer to the application 8.1-8.6;
Coding
Assembly unit
1-1
Outdoor unit: master
1-2...1-n
Outtdoor unit: slave
2
Y-shape filter
3
Stop valve (field supply)
4
Wired controller
6
Drain valve (field supply)
7
Fill valve (field supply)
8
Balance tank (field supply)
8.1
Air purge valve
8.2
Drain valve
9
Expansion vessel (field supply)
10
P_o: Outside circulation pump (field supply)
11
Collector / distributor (field supply)
12
Domestic hot water tank (field supply)
12.1
Air purge valve
12.2
Heat exchanger coil
12.3
Booster heater
The volume of balance tank (8) should be greater than (40*n)L. The drain valve (6) should be installed at the lowest
positon of the system.
The water inlet and outlet pipe joints of each unit of the parallel system should be connected with soft connections,
and one-way valves must be installed at the water outlet pipe;
The Tbt1 temperature sensor must be installed in the parallel system (otherwise unit cannot be started), the
temperature point is set in the balance tank (8).
22T÷30T
Coding
FHL 1...n
FCU 1...n
NOTE
Cod. 3QE47660 - Rev. 00 - 02/2022
Assembly unit
13
T5: DHW tank temp, sensor
14
Hot water tap (field supply)
15
P_d: DHW pump (field supply)
16
One way valve (field supply)
17
Bypass valve (field supply)
18
SV1: 3-way valve (field supply)
19
SV2: 3-way valve (field supply)
23
Mixing station (field supply)
23.1
SV3: 3-way valve (field supply)
23.2
P_c: zone 2 pump (field supply)
24
Tw2: Zone 2 water flow temp, (individual purchase)
Tbt1: Balance tank temp, sensor (individual
25
purchase)
Floor heating loop (field supply)
Fan coil units (field supply)
AHS
Additional heating source (boiler) (field supply)
/
/
/
/
101
EN