8.7 Application 7
The units are installed in parallel and can be used for cooling, heating and hot water.
•
6 units can be connected in parallel. Please refer to 9.7.5 for the parallel system electrical control system connection
diagram.
•
The parallel system can control and view the operation of the entire system only by connecting the master to the wire
controller;
•
If the DHW function is required, the water tank can only be connected to the master unit water circuit through a three-way
valve, and controlled by the master unit;
•
If you need to link with AHS, the AHS can only be connected to the master waterway and controlled by the master unit;
•
The connection and function of the terminal are the same as the single unit, please refer to the application 8.1-8.6;
Coding
Assembly unit
1-1
Outdoor unit: master
1-2...1-n
Outtdoor unit: slave
2
Y-shape filter
3
Stop valve (field supply)
4
Wired controller
6
Drain valve (field supply)
7
Fill valve (field supply)
8
Balance tank (field supply)
8.1
Air purge valve
8.2
Drain valve
9
Expansion vessel (field supply)
10
P_o: Outside circulation pump (field supply)
11
Collector / distributor (field supply)
12
Domestic hot water tank (field supply)
12.1
Air purge valve
12.2
Heat exchanger coil
12.3
Booster heater
•
The volume of balance tank (8) should be greater than (40*n)L. The drain valve (6) should be installed at the lowest
positon of the system.
•
The water inlet and outlet pipe joints of each unit of the parallel system should be connected with soft connections,
and one-way valves must be installed at the water outlet pipe;
•
The Tbt1 temperature sensor must be installed in the parallel system (otherwise unit cannot be started), the
temperature point is set in the balance tank (8).
22T÷30T
Coding
FHL 1...n
FCU 1...n
NOTE
Cod. 3QE47660 - Rev. 00 - 02/2022
Assembly unit
13
T5: DHW tank temp, sensor
14
Hot water tap (field supply)
15
P_d: DHW pump (field supply)
16
One way valve (field supply)
17
Bypass valve (field supply)
18
SV1: 3-way valve (field supply)
19
SV2: 3-way valve (field supply)
23
Mixing station (field supply)
23.1
SV3: 3-way valve (field supply)
23.2
P_c: zone 2 pump (field supply)
24
Tw2: Zone 2 water flow temp, (individual purchase)
Tbt1: Balance tank temp, sensor (individual
25
purchase)
Floor heating loop (field supply)
Fan coil units (field supply)
AHS
Additional heating source (boiler) (field supply)
/
/
/
/