5 IMPORTANT INFORMATION FOR THE REFRIGERANT
This product has the fluorinated gas, it is forbidden to release to air.
Refrigerant type: R32; Volume of GWP: 675.
GWP=Giobal Warming Potential
Model
22T
26T
30T
Frequency of Refrigerant Leakage Checks
- For unit that contains fluorinated greenhouse gases in quantities of 5 tonnes of CO
than 50 tonnas of CO
equlvalent,at least every 12 months, or where a leakage detection system Is lnstaled, at least
2
avery 24 months.
- For unit that contains fluorinated greenhouse gases in quantities of 50 tonnes of CO
than 500 tonnes of CO
equivalentat least avery six months, or where a leakage detection system is installed, at least
2
every 12 months.
- For unit that contains fluorinated greenhouse gases in quantities of 500 tonnes of CO
every three months, or where a leakage detection system is installed,at least every six months.
- This air-conditioning unit Is a hermetically sealed equipment that contains fUorlnated greenhouse gases.
- Only certificated person Is allowed to do Installation, operation and maintenance.
6 INSTALLATION SITE
There is flammable refrigerant in the unit and it should be instaled in a well-ventilated site. If the unit is installed inside,
an additional refrigerant detection device and ventilation equipment must be added in accordance with the standard
EN378. Be sure to adopt adequate measures to prevent the unit from being used as a shelter by small animals.
Small animals making contact with electrical parts can cause malfunction, smoke or ftre. Please instruct the custom er
to keep the area around the unit clean.
Select an installation site where the following condition sare satisfied and one that meets with your customer's approval.
- Places that are wall-ventilated.
- Places where the unit does not disturb next-door neighbors.
- Safe places which can bear the unirs weight and vibration and where the unit can be installed at an even level.
- Places where there is no possibility of flammable gas or product leak.
- The equipment is not intended for use in a potentially explosive atmosphere.
- Places where servicing space can be well ensured.
- Places where the units' piping and wiring lengths come within the allowable ranges.
- Places where water leaking from the unit cannot cause damage to the location (e.g. in case of a blocked drain pipe).
- Places where rain can be avoided as much as possible.
- Do not install the unit in places often used as a work space. In case of construction work (e.g. grinding etc.} where a lot of
dust is created, the unit must be covered.
- Do not place any object or equipment on top of the unit (top plate)
- Do not climb, sit or stand on top of the unit.
- Be sure that sufficient precautions are taken in case of refrigerant leakage according to relevant local laws and
regulations.
- If the external unit needs to be installed near the coast or where corrosive gases are present, its durability may decrease.
In the event of installations near the coast, we recommend avoiding the installation of the unit directly exposed to sea
winds.
When installing the unit in a place exposed to strong wind, pay special attention to the following.
88
EN
OMNIA M 3.2
Factory charged refrigerant volume in the unit
Refrigerant/kg
5.00
5.00
5.00
CAUTION
WARNING
Cod. 3QE47660 - Rev. 00 - 02/2022
22T÷30T
Tonnes CO
equivalent
2
3.38
3.38
3.38
equivalent or more,but of less
2
equivalent or more, but of lass
2
equivalent or more, at least
2