ALARMS
W145
High motor temperature
W146
Motor overtemperature
W148
Lock overcurrent
W150
Opening obstacle
W151
Closure obstacle
W152
Door locked in closure
W153
Door locked in opening
W256
Board on
W257
Start software board
W320
Maintenance event
START-UP PROCEDURE FOR AUTOMATIC SWING DOOR
Preliminary checks
At the end of the installation activities, manually move the doors and check movement is regular and friction free.
Check the structure is solid and correctly fasten all the screws.
Check the electrical connections are all correct.
- Before connecting possible safety devices, leave the jumpers on the safety terminals of the electronic control (TS-CS, TS-OS).
N.B. The first opening and closure manoeuvre is carried out with low speed to enable automatic detection of the stop measurements.
- To ensure the electronic control has the factory settings, restore the values using the menu:
MEM > FSET > YES (confirm by pressing ENTER for 1 second).
- Execute menu adjustments as indicated in chapter 9. Use the OPEN key to give the opening commands and check the door is working properly.
N.B. The automation automatically recognises possible obstacles during the closure (movement inversion) and opening manoeuvre (movement stoppage).
- Connect the command and safety devices one at a time to protect the door closure manoeuvre, as indicated in chapter 8.5 and checking its correct operation.
N.B. Check the passage compartment is correctly protected from safety sensors, in compliance with the provisions of the European standard EN16005 (Annex C).
- Connect the safety devices one at a time to protect the door opening manoeuvre, as indicated in chapter 8.6 and checking its correct operation.
N.B. In the event of distances between the door and the fixed parts, comply with the European standard EN16005 (chapter 4.6.2.1.a), the safety sensors in opening are not
necessary (X ≤ 100 e Y ≥ 200).
- Connect the functions selector as indicated in chapter 9.4.
- When start-up is complete, deliver the use instructions to the manager of the automatic door, including the warnings and information necessary to maintain safety and
functionality of the automatic door.
N.B. The manufacturer of the automatic leaf door must add its identification label of the system.
Other than the following list of possible problems, the warnings are provided on the display.
FAULTS SEARCH
Problem
The automation does not open or close.
The automation does not execute the
functions set.
Movement of the doors is not linear or
movement is inverted for no reason.
The automation opens but does not close.
Manoeuvre speed lowered to safe value [15°/s]
Door stopped until the motor temperature returns to safe values
Anomalous lock power supply current (too high)
Obstacle detected during opening manoeuvre. The door stops and closes once the automatic
closure time is up
Obstacle detected during closure manoeuvre. The door reopens
Door cannot start opening manoeuvre. The door does not accept commands for 5s
Door cannot start closure manoeuvre. The door does not accept commands for 5s
Enabled once the automation has executed the specified number of manoeuvres from the
maintenance parameter
Possible cause
No mains power supply (display off).
Accessories outside the short circuit.
The door is locked with latches or locks.
Functions selector with wrong setting.
Command or safety devices are always enabled.
Automation did not correctly detect the stop
measurements.
The safety devices test causes anomalies.
The opening devices are enabled.
Automatic closure is not working.
Intervention
Check the mains power supply is present.
Disconnect all the accessories from the terminals
-24V/+24V and reconnect them one at a time (check the
presence of 24V voltage).
Check the doors move freely.
Check and correct the functions selector settings.
Disconnect the devices from the terminal boards and
check the door is working.
Reset by switching the automation off and back on.
Bridge one contact at a time TS/OS TS/CS.
Check the opening sensors are not subject to vibrations,
do not make false detections or the presence of objects
in motion in the action range.
Check the settings of the functions selector.
19