Operating Range - AERMEC VED I Serie Manual De Uso E Instalación

Ventiloconvector para instalación horizontal y vertical con canales
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

3.

OPERATING RANGE

Maximum recommended entering water temperature
(main coil)
Minimum flow rate (main coil)
Maximum flow rate (main coil)
Minimum flow rate (heating only coil accessory)
Maximum flow rate (heating only coil accessory)
Maximum recommended entering water temperature
(main coil)
Minimum flow rate (main coil)
Maximum flow rate (main coil)
Minimum flow rate (heating only coil accessory)
Maximum flow rate (heating only coil accessory)
The earth leakage of several units con-
nected to one circuit breaker is added.
It is recommended to check the rating
of the circuit breaker and it may be
Water temperature
In order to avoid air stratification and there-
fore achieve better mixing it is advised not
supply the fan coil unit with water hotter
than 65°C.
Minimum average water temperature
If the fan coil unit operates continuously
in cooling mode in a room with high
relative humidity, condensate might form
on the air discharge and unit casing. This
condensate might be deposited on the
floor and on any objects underneath. To
prevent the formation of condensation
on the exterior of the unit while the fan
is operating, the average water tempera-
ture should not drop below the operating
MINIMUM AVERAGE WATER TEMPERATURE [°C]
Ambient wet bulb temperature
22
4880950_03 - 1811
VED
VED
necessary to split the installation into
several circuits, each having its own
circuit breaker.
The use of very hot water could cause creak-
ing due to the thermal expansion of the
different components (plastics and metals).
This does not cause damage to the unit if
the maximum operating temperature is not
limits shown in the table below, deter-
mined by the room ambient conditions.
These limits refer to unit operation with
fan at minimum speed.
In the case of prolonged periods with the
fan switched off and cold water passing
through the coil the formation of con-
densate on the unit casing is possible.
030I
040I
130I
°C
l/h
150
150
150
l/h
1500
1500
1500
l/h
50
-
50
l/h
500
-
500
530I
540I
532I
°C
l/h
300
300
300
l/h
3000
3000
3000
l/h
-
-
200
l/h
-
-
2000
21
23
15
3
3
17
3
3
19
3
3
21
6
5
23
-
8
140I
230I
240I
65
150
150
150
1500
1500
1500
-
50
-
-
500
-
541I
730I
740I
65
300
300
300
3000
4500
4500
100
-
-
1500
-
-
exceeded.
In this case the installation of the 3 way
valve accessory is recommended.
Ambient dry bulb temperature
25
27
3
3
3
3
3
3
4
3
7
6
330I
340I
300
400
3000
4000
100
-
1000
-
732I
741I
300
300
4500
4500
300
300
2500
3000
29
31
3
3
3
3
3
3
3
3
5
5