8.8.
CONDENSATE DISCHARGE CONNECTION
Ø est. 20,5mm / 0.81"
8.9.
DUCT CONNECTIONS TO THE UNIT
The VED unit is designed for ducted connec-
tions.
To identify the duct connections refer to
the drawings.
32
4880950_03 - 1811
The fan coil unit drain pan has two con-
densate discharge outlet (left and right
side).
It is recommended to use the conden-
sate drain connection on the side of the

hydraulic connections.

Mount the condensate discharge drain
connection provided loose. Care should be
taken to seal the fitting between the drain
pan and the drain connection with silicone
sealant.
Seal the drain not used.
Connect the drain pan fitting to the con-
densate drain system. Use a drain tube
that must be connected to the condensate
discharge fitting. The condensate drains
are designed to be connected only by flex-
ible tubes of adequate internal diameter,
avoid imposing additional load and do not
use them for any other purposes.
Ensure that the drain not used is sealed
Connect the ducting to the connections us-
ing straps.
Ensure that the filter is always mounted on
the unit during operation, otherwise the
and has no leaks.
The condensate drain system must be
appropriately sized and the piping posi-
tioned in such a way to maintain a slope
(min. 1%).
To avoid unpleasant smells a trap is recom-
mended if the condensate is connected to
the sewage system.
Carry out a functional and leak test of the
installation by pouring water into the drain
pan.
dust in the air will dirty the coil.