ProCore Edge 30 North America
Display
Message
MODULE
OVER TEMP
(Module /
Charger Over
Temperature)
Module OVP
Tripped
MODULE TYPE
ERR
(Module
Installation
Type)
No Battery
Configuration
No Modules
OCP Fault
(There is a
Module
Overcurrent)
5912995 A01
Message
Description
type
The air intake is blocked.
The system board
temperature sensor is
above 80° C.
Fault
The module temperature is
too high to charge.
The module failed.
There was an error in the
Fault
over-voltage protection
module.
The power module type
does not match the factory
configuration (cabinet
Fault
voltage) settings, or
incompatible modules were
installed together.
The parameters have not
Fault
been configured for the
voltage mode charge.
No power modules are
Fault
installed.
Fault
The module failed.
64 of 68
Action(s)
Check for obstructed air flow.
Remove the blockage.
Replace the power module.
Check that the battery
voltage is within range for
the charger.
Install the correct
power module.
Call Webasto service.
Configure the voltage
mode settings on the
charger, using the ProCore
mobile app.
Call Webasto service.
Replace the power module.