Step
Action/Display Indication
9
If necessary, change "P0298 - Application"
parameter. This change will affect P0156,
P0157, P0158, P0401, P0404 and P0410
(this last one only if P0202 = 0, 1 or 2 - V/f
modes). The time and level of the IGBT
overload protection will also be affected.
Press the
key to the next parameter.
11
If necessary, change "P0398 - Motor
Service Factor" parameter. This change
will affect the current and the time of the
motor overload protection operation.
Press the
key to the next parameter.
13
If necessary, change "P0401 - Motor
Rated Current" parameter. This change
will affect P0156, P0157, P0158 and P0410.
Press the
key to the next parameter.
15
If necessary, change "P0403 - Motor
Rated Frequency" parameter. This change
will affect P0402.
Press the
key to the next parameter.
First Time Power-Up and Start-Up
Step
Action/Display Indication
10
If necessary, change "P0202 - Control
Type" parameter. This guide will only
show the setting for P0202 = 0 (V/f 60 Hz)
or P0202 = 1 (V/f 50 Hz). Refer to the
programming manual for other settings
(V/f Adjustable, V V W or Vector Modes).
Press the
key to the next parameter.
12
If necessary, change "P0400 - Motor
Rated Voltage" parameter. This change
corrects the output voltage by the factor
"x = P0400/P0296".
Press the
key to the next parameter.
14
If necessary, change "P0404 - Motor
Rated Power" parameter. This change will
affect P0410.
Press the
key to the next parameter.
16
If necessary, change "P0402 - Motor
Rated Speed". This change will affect
P0122 to P0131, P0133, P0134, P0135,
P0182, P0208, P0288 and P0289.
Press the
key to the next parameter.
CFW700 | 51