4-way Air Discharge Cassette Type
Installation of ceiling panel
(Sold separately)
Install the ceiling panel according to Installation
Manual attached with it after piping/wiring work
has completed.
Check that installation of indoor unit and ceiling
opening part is correct, and then install it.
REQUIREMENT
• Joint the connecting sections of ceiling panel,
ceiling surface, ceiling panel and indoor unit
closely.
Any gap between them will cause air leakage
and the generate condensation or water
leakage.
• Remove the adjust corner caps at the four
corners of the ceiling panel, and then install the
ceiling panel onto the indoor unit.
• Make sure that the claws of the four adjust
corner caps are securely fit.
* Improper fitting of the claws may cause
water leakage.
Installation of remote
controller
(Sold separately)
For installation of the wired remote controller,
follow the Installation Manual attached with the
remote controller.
• Pull out the remote controller cord together with
the refrigerant pipe or drain pipe.
Be sure to pass the remote controller cord
through upper side of the refrigerant pipe and
drain pipe.
• Do not leave the remote controller at a place
exposed to the direct sunlight and near a stove.
11-EN
In case of wireless type
The sensor of indoor unit with wireless remote
controller can receive a signal by distance within
approx. 7m. Based upon it, determine a place
where the remote controller is operated and the
installation place.
• Operate the remote controller, confirm that the
indoor unit receives a signal surely, and then
install it.
• Keep 1m or more from the devices such as
television, stereo, etc.
(Disturbance of image or noise may generate.)
• To prevent a malfunction, select a place where
is not influenced by a fluorescent light or direct
sunlight.
• Two or more (Up to 6 units) indoor units with
wireless type remote controller can be installed
in the same room.
– 11 –