+00EH99858901_01EN_4-way_IM_printOnly.book Page 14 Tuesday, December 4, 2007 2:31 PM
4-way Air Discharge Cassette Type
After the check, the drain pump motor runs,
connecting the float switch connector.
(In case of check by pulling out the float switch
connector, be sure to return the connector to the
original position.)
CN34
(RED)
Black
Perform heat insulating
• As shown in the figure, cover the flexible hose
and hose band with the attached heat insulator
up to the bottom of the indoor unit without gap.
• Cover the drain pipe seamlessly with a heat
insulator to be procured locally so that it
overlaps with the attached heat insulator of the
drain connecting section.
Wrap the attached heat insulator seamlessly from
the surface of the indoor unit.
* Direct the slits and seams of the heat insulator
upward to avoid water leakage.
Single phase
220–240V
Power
terminals
1
2
White
Red
Black
Pull out connector CN34 (Red)
from P.C. board.
Heat insulator of the
Heat insulator (to
drain connecting
be procured locally)
section (Accessory)
– 14 –
Installation Manual
EN
14-EN
Toshiba XXXXXXX(X/X)