+00EH99858901_01EN_4-way_IM_printOnly.book Page 7 Tuesday, December 4, 2007 2:31 PM
4-way Air Discharge Cassette Type
REQUIREMENT
• When using the air conditioner with 2-way/3-way discharge system, a strong wind blows directly if the
ceiling height is lower than the standard.
Therefore, change the setting switch according to height of the ceiling.
• When using the high ceiling (1) or (2) with 4-way discharge system, the draft is apt to be felt due to
drop of the discharge temperature.
▼ Height list of ceiling possible to be installed
Model RAV-
No. of discharge direction
Standard (at shipment)
High ceiling (1)
High ceiling (2)
The lighting time of the filter sign (notification of filter cleaning) on the remote controller can be changed
according to installation conditions.
When it is difficult to obtain satisfactory heating due to location place of the indoor unit or the structure of
the room, the detection temperature of heating can be raised.
Discharge direction
As shown in the figure below, air discharge directions can be selected according to the shape of the room
and the location of the indoor unit installation.
• Use a shielding plate kit (sold separately) to change discharge directions.
Discharge directions are limited. Follow the Installation Manual supplied with the shielding plate kit.
7-EN
SM56 Type
SM80 Type
4-way
3-way
2-way
4-way
2.8
3.2
3.5
3.0
3.2
3.5
3.8
3.3
3.5
3.8
3.6
3 directions
– 7 –
Installation Manual
SM110, SM140 Type
3-way
2-way
4-way
3-way
3.3
3.6
3.9
4.2
3.5
3.8
4.2
4.4
3.8
4.5
4.6
2 directions
Shielding plate
(sold separately)
(Unit:m)
High ceiling
setup
2-way
Set data
4.5
0000
4.6
0001
0003