+00EH99858901_01EN_4-way_IM_printOnly.book Page 22 Tuesday, December 4, 2007 2:31 PM
4-way Air Discharge Cassette Type
3
Procedure
Using temp. setup
CODE No. [
4
Procedure
Using timer time
SET DATA [
5
Procedure
Push
button. When the display changes from
flashing to lit, the setup is completed.
• To change settings of another indoor unit,
repeat from Procedure
• To change other settings of the selected indoor
unit, repeat from Procedure
Use
button to clear the settings.
To make settings after
repeat from Procedure
6
Procedure
When settings have been completed, push
button to determine the settings.
When
button is pushed, "SETTING" flashes
and then the display content disappears and the
air conditioner enters the normal stop mode.
(While "SETTING" is flashing, no operation of the
remote controller is accepted.)
When installing separately
sold filters
Be sure to make ceiling setting when installing
separately sold filters.
* Separately sold filters cannot be installed in an
indoor unit on a high ceiling.
Follow to the basic operation procedure
1
2
3
→
→
→
(
• For the CODE No. in Procedure
• For the set data in Procedure
data of filters to be installed from the following
table.
Setup data
0000
Setup data
0003
/
buttons, specify
].
/
buttons, select
].
2
.
3
.
button was pushed,
2
.
4
5
6
→
→
).
3
, specify [5d].
4
, select the setup
High-ceiling setting
Normal filter
(Installed at factory shipping)
High-ceiling setting
High Efficiency Filter (65%)
High Efficiency Filter (90%)
– 22 –
Installing indoor unit on
high ceiling
When an indoor unit is installed on a ceiling higher
than the standard height, make the high-ceiling
setting for air volume adjustment.
• Take the same procedure as that in "When
installing separately sold filters".
• Select the setting data for Procedure
"Height list of ceiling possible to be installed"
table on page 7 in this manual.
When wireless remote
controller is used
Change the high-ceiling and filter settings with the
DIP switch on the receiver section P.C. board.
For details, refer to the manual of the wireless
remote controller kit. The settings can also be
changed with the switch on the indoor
microcomputer P.C. board.
* However, once the setting is changed, setting to
0001 or 0003 is possible but setting to 0000
requires a setting data change to 0000 using the
wired remote controller (separately sold) with
the normal switch setting (factory setting).
SW501-1
SW501-2
MCU(IC501)
Setup data
SW501-1
0000
OFF
(Factory shipping)
0001
ON
0003
OFF
To restore the factory settings
To return the DIP switch settings to the factory
settings, set SW501-1 and SW501-2 to OFF,
connect a separately sold wired remote controller,
and then set the data of CODE No. [5d] to "0000"
in "When installing separately sold filters" on this
page.
Installation Manual
4
from the
EN
SW501-2
OFF
OFF
ON
22-EN
Toshiba XXXXXXX(X/X)