Performance Approvals
Description
PIR 7000 / 7200 remote test
adapter
PIR 7000 insect protection
PIR 7000 hydrophobic filter
PIR 7000 calibration adapter 6811610
PIR 7000 / 7200 POM pro-
cess adapter (polyoxymethy-
lene)
PIR 7000 assembly set
Terminal box Ex e
Terminal box Ex d
Magnetic wand
1) Check firmware compatibility of sensor and gas detector. Changing
the PCB unit may require a firmware update. Contact Dräger for sup-
port.
17.5.1 Sensors
Check firmware compatibility of sensor and gas detector.
Changing the sensor may require a firmware update. Contact
Dräger for support.
Description
Dräger PIR 7000 type 334
(NPT)
Dräger PIR 7000 type 340
(NPT)
Dräger PIR 7000 334 (M25)
complete set
Dräger PIR 7000 340 (M25)
complete set
Dräger PIR 7200 (NPT)
Dräger PIR 7200 (M25)
HART
complete set
18
Performance Approvals
In combination with certain sensors, Polytron 8xx0 is
performance approved based on the following standards:
– EU and Type Examination Certificates in line with
EN 60079-29-1, EN 50104, EN 45544 and DIN
IEC 62990-1. Issued by DEKRA Testing and Certification
GmbH, Handwerkstr. 15, D-70565 Stuttgart.
– FM performance approval in line with ANSI/ISA-92.00.01
FM6340
For further information on sensor specifications and
restrictions (e.g., measuring principles, performance, cross-
sensitivity), refer to the instructions for use for the relevant
sensor.
46
Part number
6811630 / 6811930
6811609
6811890
6811915
6811648
6811989
4520561
4544101
Part number
6811822
6811832
6811825
6811819
6811572
6812290
18.1 EU-TYPE Examination Certificate,
BVS 13 ATEX G 001 X
Measurement of flammable gases and vapors mixed with air.
– Polytron 8200 CAT with DrägerSensor DQ
Special conditions:
● When streaming with air containing measured gas,
measured values may increase by up to 32 %.
● When operating with the DQ remote calibration
adapter, measured values may increase by up to
70 %.
– Polytron 8200 CAT with DrägerSensor LC
Approved with 10 %LEL full scale deflection.
A connection to a controller with approved measuring
function (e.g., REGARD
alarms for over range measured values must be activated
at the controller.
– Polytron 8310 IR with DrägerSensor IR
– Polytron 8700 IR with PIR 7000 type 334 and 340
Measurement of oxygen (inertization)
– Polytron 8100 EC with DrägerSensor O
DrägerSensor O
LS (6809630) within a measuring range
2
of 0-5...25 Vol% O
.
2
Approved are:
– 4 to 20 mA interface
– Relay module
– Remote sensor
– HART
– Factory default full scale deflections
Not approved are the fieldbus interface and the data logger.
18.2 Type Examination Certificate, PFG 14
G 001 X
Measurement of oxygen (deficiency and excess oxygen)
– Polytron 8100 EC with DrägerSensor O
DrägerSensor O
LS (6809630) within a measuring range
2
of 0–25 Vol% O
.
2
Measurement of hydrogen sulfide
– Polytron 8100 EC with Dräger SensorAlive (6809630)
within the following measuring ranges:
● 0.5 - 100 ppm (Type HM)
● 0 - 100 ppm (Type SM)
Measurement of carbon dioxide
– Polytron 8720 IR with PIR 7200 within the following
measuring ranges:
● 1 Vol% and 10 Vol% – EN 45544-2
● 2000 ppm, 1 Vol% and 10 Vol% – EN 45544-3
Approved are:
– 4 to 20 mA interface
– Relay module
– Remote sensor
Instructions for use
®
7000) is required. Latching
(6809720) and
2
(6809720) and
2
®
|
Dräger Polytron
8000 Series