CONTROL BOX
F
eatures
•
Under-voltage detection.
•
Air pressure monitoring with functional check of the air pressure
switch during start-up and operation.
•
Device release button with multi-coloured LED (A).
•
Remote-controlled release button (8).
•
Indicator in various colours of fault and operational condition
messages.
•
Limitation of repetitions.
•
Intermittent operation checked every 24 hours maximum of conti-
nuous operation (the device will automatically initiate a controlled
shutdown followed by a restart).
DANGER
Risk of electrocution.
Check the air pressure switch connection lines (terminals 3, 6
and 11) for short circuits.
!
CAUTION
All operations must be performed exclusively by qualified
personnel.
Before making any type of modification to the wiring in the
connection area, isolate the system completely from the mains
supply.
Secure the system against accidental restart and ensure that
there is no voltage.
IMPORTANT
Check the condition of the wiring after each service performed.
Equipment or programmer
LME 22.233 C2
LME 22.331 C2
t1
Preventilation time
t3
Pre-ignition time
t3n
After-ignition time
t4
Interval between ignition and release of «BV2»
t11
Programmed opening time for actuator «SA»
t12
Programmed closing time for actuator «SA»
TSA Ignition safety time
0006160660_202402
TSA
t1
s
s
3
20
3
30
t
echnIcal data
Mains voltage
Mains frequency
Absorption
External primary fuse (Yes)
Protection rating
Installation position
Input current at terminal 12
Safety class
Repetition time in the event of loss of flame
Weight
Admissible temperature
t3
t3n
s
s
3
2,5
3
2,5
ENGLISH
A
8
AC 120 V -15% / +10%
AC 230 V -15% / +10%
50... 60 Hz ±6%
12 VA
Max. 10 A
IP40
Any
Max. 5 A
I
Max. 1"
0.16 kg
-20....+60°C
t4
t11
s
s
8
30
8
12
t12
s
30
12
13 / 40