emarKs regardIng FIrst IgnItIon
After first ignition or after any maintenance work, carry out the following safety checks:
Burner start with previously interrupted flame detector line
Burner operation with flame loss simulation. To this end, interrupt the fuel supply
Burner operation with air pressure drop simulation
After each non-modifiable lock-out, the red light comes on.
IMPORTANT
To identify the error code, please refer to the section "Faulty Operation - causes - solutions".
16 / 40
Safety checks
Expected result
Lock-out cannot be modified at the end of the safety time
Lock-out cannot be modified
Lock-out cannot be modified