EQUIPMENT OPERATING PROBLEMS
In case of a lockout that cannot be changed, the fuel valve outputs, burner motor and ignition device are switched off (< 1 s).
In case of a malfunction, the equipment performs the following actions:
1
Voltage below the minimum voltage threshold (AC 165 V)
2
Voltage still below the minimum voltage threshold (AC 175 V)
3
Parasitic light during the pre-ventilation interval (t1)
4
Parasitic light during the wait time (tw)
5
No flame at the end of the safety time (TSA)
6
7
Air pressure switch stuck in operating position
8
Air pressure switch stuck in rest position
9
Air pressure drop at the end of the specified time (t10) and during
10
CPI contact is open during the interval (tw)
11
(tw) Waiting time
(t1) Pre-ventilation time
(t10) Specified time for air pressure signal
(TSA) Safety time
IMPORTANT
After each non-modifiable lock-out, the LME device stops. The equipment indicator light is steady on red.
The burner control can be released immediately.
This status is also maintained in case of power failure.
0006160660_202402
CAUSE
Power supply interruption
No flame during operation
operation
RESPONSE
Restart
Safety switching off
Restart
Lock-out cannot be modified
Lockout upon start, lockout cannot be changed after max. 30"
Lock-out cannot be modified at the end of the safety time
Lock-out cannot be modified
Lockout upon start, lockout cannot be changed after maximum 65"
Lockout not modifiable about 180" after expiry of the specified time (t10)
Lock-out cannot be modified
Lockout upon start, lockout cannot be changed after maximum 60"
ENGLISH
39 / 40