STARTING UP AND REGULATION
START-UP WARNING NOTES
Wear protective clothing with electrostatic
properties.
•
Start up, test and maintenance of the equipment must only be
carried out by qualified technicians, in compliance with current
regulations.
•
Once the burner is fixed to the heat generator, make sure that the
generated flame does not come out of any slot during testing.
•
Check equipment fuel supply pipe seal.
•
Check that fuel flow rate equals the power required to the burner.
•
Set the burner fuel capacity to the power required by the heat
generator.
•
Fuel supply pressure must be within the values indicated on the
plate on the burner and/or manual
•
Check that the fuel supply system is suitably sized for the flow
required by the burner and that it has all the safety and control
devices required by current standards.
•
Check that all terminals on the power supply conductors are
properly tightened.