Charger power supply connection
8.2. Cabling requirements
To guarantee the safety of persons, for the unit to function correctly and comply with the applicable standards, the
unit must be connected to the ground of the installation.
The AC connection must comply with section 8.3. The installation must use single-pole cables with a copper or
aluminum conductor.
CAUTION
If using aluminum cables, the installer must provide the necessary means to prevent galvanic coupling (bipolar
terminals, bimetallic interfaces, etc.).
The dimensioning of the ground wiring will be the responsibility of the installer and must meet applicable
regulatory requirements in the installation.
The connection allows a cable section of between 35 mm
ground connection. The range of admissible diameters for the input cables is between 15 and 20 mm. The cable
should be passed through the cable gland before mounting the terminal.
300000772 - Monterings- och bruksanvisning
Image of the IP2X protection of the connection
and 95 mm
2
and between 25 mm
and 70 mm
2
2
Ingeteam
EN
ES
FR
IT
SV
for the
2
51

Publicidad

loading