1
Electric box
2
Water connections
3
UNIT DESCRIPTION
Comfort, low noise, and efficiency in perfect harmony!
The new series of hydronic cassette units ACQVARIA, with ON/
OFF motor, consists of 6 models (10-20-30-40-50-60) for 2-pipe
systems and 6 models (10-20--30-35-40-60) for 4-pipe systems.
The engineering of the unit makes it possible to develop up to 5
kW in the cooling mode in a standard 600x600 mm modular sus-
pended ceiling and over 9 kW in the 860x860 mm modularity,
with exceptionally low noise levels in the phases for maintaining
interior comfort.
ACQVARIA leverages the entire Galletti, MYCOMFORT, EVO , and
TED microprocessor controller platform that incorporate sophis-
ticated adjustment logics based on air temperature, air humidi-
ty, and water temperature.
These benefits translate into greater accuracy in achieving and
maintaining the desired comfort conditions through appropri-
ate modulation of the fan speed as well as the reduction of noise
emissions, which adapt to the actual thermal load.
The suspended ceiling unit houses all the components, heat ex-
change coil, fan drive assembly, and condensate collection and
drainage system. Its structure is designed for introducing fresh
air into the space, mixing it with recovered air, and distributing
the treated air from the cassette unit to adjacent rooms.
Two tipes of intake and oulet air grilles:
Standard grill: ABS material, available in RAL9003 or RAL9010
guarantee optimal integration into the suspended ceiling
panels.
» Installation AQ 40-50-60
1
Electric box
2
Water connections
OPERATING LIMITS
Thermal carrier fluid: water
Water temperature: 5°C ÷ 80°C
Air temperature: 5°C ÷ 43°C
Supply voltage: 230 V - 50 Hz
Maximum water pressure during operation: 10 bar
Relative humidity limit of the ambient air:RH < 75% not
condensing
Effetto gille : design grille with Coanda effect: DIBOND ma-
terial with possibility to configurate the color, thanks to Coanda
effect, the air is expelled parallel to the ceiling, cooling the walls
before mixing with the ambient air at the ground. In this way the
operation will be optimized during the summer, ensuring more
comfort for the occupants.
Both with easy access to air filter for cleaning operations.
The unit can be supplied complete with valves, including pres-
sure-independent balancing and control valves, the use of
which significantly reduces commissioning time.
3.1
AVAILABLE VERSIONS
AQ0B0 - Unit with one coil for 2-pipe systems
AQ0BB - Unit with one coil for 4-pipe systems
Accessories supplied with the unit
Ū Auxiliary water drip tray;
Ū Installation and use manual;
Ū Brackets for securing the unit.