ACCESSORIES
8.1
2- OR 3-WAY MOTOR-DRIVEN VALVE KITS
B
WARNING: The installation of a valve kit on the fan coil unit
is mandatory ACQVARIA.
The kit is made up of:
Ū Brass 2- or 3-way valve with 4 connections with built-in by-
pass, maximum operating pressure 16 bar.
Ū Electrothermal actuator with 230 V or 24 V power supply,
ON/OFF (or modulating) function, total opening time 3 min-
utes.
Ū Hydraulic kit with O-ring for connection with the exchanger
and paper gasket for connection with the valve
Ū Brackets for fastening the hydraulic kit on the side of the unit
in order to ensure stability during transport if the valves are
already installed.
Unit
AQ10Q0B0, AQ20Q0B0, AQ30Q0B0 (2 pipes)
AQ40Q0B0,AQ50Q0B0, AQ60Q0B0 (2 pipes)
Unit
AQ10Q0BB, AQ20Q0BB, AQ30Q0BB, AQ35Q0BB (4 tubi)
AQ40Q0BB, AQ60Q0BB (4 pipes)
Unit
AQ10Q0B0, AQ20Q0B0, AQ30Q0B0 (2 pipes)
AQ40Q0B0, AQ50Q0B0, AQ60Q0B0 (2 pipes)
Unit
AQ10Q0BB, AQ20Q0BB, AQ30Q0BB, AQ35Q0BB (4 tubi)
AQ40Q0BB, AQ60Q0BB (4 pipes)
8.2
PRESSURE-INDEPENDENT MOTOR-DRIVEN 2-WAY VALVE KIT
B
WARNING: The installation of a valve kit on the fan coil unit
is mandatory ACQVARIA.
The pressure-independent 2-way valve kit consists of:
Ū 2-way valve with maximum operating pressure of 16 bar.
Ū Electrothermal actuator with 230 V or 24 V power supply, ON/
OFF (or modulating) function, total opening time 3 minutes.
Unit
AQ10Q0B0, AQ20Q0B0, AQ30Q0B0 (2 pipes)
AQ40Q0B0, AQ50Q0B0, AQ60Q0B0 (2 pipes)
Unit
AQ10Q0BB, AQ20Q0BB, AQ30Q0BB, AQ35Q0BB (4 tubi)
AQ40Q0BB, AQ60Q0BB (4 pipes)
8.3
AUXILIARY WATER DRIP TRAY FOR COLLECTING CONDENSATE FROM THE CONTROL VALVES
The auxiliary water drip tray is supplied with the base unit to-
gether with two fastening screws.
Its function is to collect the condensate generated by the control
valves and to convey it inside the main condensate drip tray of
the unit. (FIGURE 15, FIGURE 16)
C
The valve kits are shown in the figures from page: 13.38  p. 158.
Pressure drops of the valve/hydraulic kit assembly are calculated
using the following formula:
∆P
W
W
∆P
W
Q
W
K
V
table
Valve type
Connection
3-way
3/4'' M
3-way
3/4'' M
Cooling
Valve type
Connection
KVS direct way
3-way
3/4'' M
2,5
3-way
3/4'' M
4
Valve type
Connection
2-way
3/4'' M
2-way
3/4'' M
Cooling
Valve type
Connection
2-way
3/4'' M
2-way
3/4'' M
Ū Hydraulic kit with O-ring for connection with the exchanger
Ū Brackets for fastening the hydraulic kit on the side of the unit
The valve kits are shown in the figures on page: 13.46  p. 162
and 13.49  p. 164.
Valve type
Connection
2-way
3/4'' M
2-way
1 1/4 '' M
Cooling
Valve type
Connection
2-way
3/4'' M
2-way
1 1/4 '' M
NOTE:
for units AQ10-AQ20-AQ30-AQ35 it is necessary to in-
stall the 3-way valves inclined so as to comply with the space
constraint regarding the height of the base unit.
= (Q
/ K
)
2
W
V
h
e
=
pressure
=
water
flow
= water flow rate coefficient of the valve obtained from the
Kvs straight
2,5
4
Heating
Kvs by-pass
Connection
1,6
3/4'' M
1,6
3/4'' M
KVS
2,8
4
Heating
KVS
Connection
2,8
3/4'' M
4
3/4'' M
and paper gasket for connection with the valve.
in order to ensure stability during transport if the valves are
already installed.
Δp min [kPa]
32
20
Heating
Δp min [kPa]
Connection
16
3/4'' M
20
1'' M
r
e
:
drop
in
bar
rate
in
m
3
/h
Kvs by-pass
1,6
1,6
KVS direct way
Kvs by-pass
2,5
1,6
2,5
1,6
KVS
2,8
2,8
Δp min [kPa]
16
16
39
WC66000482-06