Descargar Imprimir esta página

Waterco MultiCyclone 12 Manual De Instalación Y Funcionamiento página 8

Prefiltración centrífuga 12 y 16
Ocultar thumbs Ver también para MultiCyclone 12:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 46
English
MULTICYCLONE PLUS TOTAL HEAD LOSS CURVE
9/12.8/
88.3
8/11.36/
78.3
7/9.95/
68.6
6/8.53/
58.8
5/7.11/
49.0
4/5.69/
39.2
3/4.27/
29.4
2/2.84/
19.6
1/1.42/
9.8
0
0
INSTALLATION
Be sure to comply with the local plumbing codes.
Be sure that all provisions for wastewater disposal meet local, state or national codes. Do not
discharge water where it will cause flooding or damage.
If the incoming water pressure is higher than the maximum operating pressure of
350kPa/3.5Bar/50psi, a Pressure Regulating Valve (PRV) must be installed upstream of the filter
inlet.
The PRV should be set to 90% of the maximum operating pressure of the tank.
If the incoming water flow is less than the filter's minimum flow requirements, the filter's filtration
efficiency will be affected, please consult Waterco.
MultiCyclone Head Loss Curve
6/100
12/200
MultiCyclone 12
18/300
24/400
Flow (m
/hr/lpm)
3
MultiCyclone 16
30/500
36/600
42/700

Publicidad

loading

Productos relacionados para Waterco MultiCyclone 12

Este manual también es adecuado para:

Multicyclone 16