Service wiring
Ground Connection: Always connect the
n
Neutral at the service to Earth Ground. If
ground is not provided by the electrical
service then a grounding stake must be in-
stalled nearby. The grounding stake must
be connected to the ground bar in the main
breaker panel and Neutral connected to
Ground at that point
400Vac(Line to Line) Three-Phase
n
This is feed from Wye-connection
power grid, the Wall Mount DC
Fast Charger can connect to L1, L2
or L3, and Neutral. Earth ground
must be connected to neutral at
only one point, usually at the
breaker panel.
Be Aware of High Voltage!
Earth Connection is Essential!