4.3) MANUALLY PROGRAMMING THE DISTANCES:
All the distances described in the previous chapter can be programmed manually:
4.3.1) Automatic limits search (all gate/door limits):
An "automatic limits search" is carried out which is identical to the "initial limits search" except that the former can be activated
at any time even if the gearmotor is already installed and the memory has correct distance values stored
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
1) Set the dip-switches as indicated; in this way the "automatic limits search" is selected.
If dip-switch 10 is OFF point "C" is positioned 5 cm from point "0", if it is ON point "C" corresponds to "0".
2) Briefly press the "CLOSE" key on the control card.
3) Wait until the search procedure has terminated (slow closing, slow opening and, lastly, fast reclosing)
4) Now that the "automatic limits search" is terminated, turn the programming switches "OFF", set the function dip-
switches on the mode required and the gearmotor is ready to use.
All the distances measured with the above procedure are memorised automatically.
Subsequent to an automatic search, if you wish to, you can modify any of the distances measured (except for distance 0) by
means of the manual search.
4.3.2) Manual search for distance "0" (Mechanical Stop in CLOSING):
The "manual search for distance 0" is carried out with this procedure, that is, you programme the maximum closing point.
1 2 3 4 5 6 7 8 9 10
1) Set the dip-switches as indicated; in this way the "manual search for distance 0" is selected.
2) Press the "CLOSE" key on the card to move the gate/door in the closing phase until the mechanical stop is reached
3) If you want, besides the "CLOSE" key, you can also press the "<<>>" key to accelerate movement.
4) When the gate/door has reached the mechanical stop, the distance has been measured so you can then proceed to
memorisation.
With this procedure the maximum closing point has been found and memorised; this measurement is fundamental because all
other measurements start from this point.
4.3.3) Manual search for distance "C" (Stopping point wanted in CLOSING):
The "manual search for distance C" is carried out with this procedure, that is, you programme the closing point you want; this is
the point at which the gate/door stops in the closing manoeuvre. When using like RO1024, this distance is normally set a few
centimetres from the mechanical stop in closing while in the case of using as CR2024, it is normally set a few millimetres from
the mechanical stop device. Obviously this distance must always be more than distance "0".
1 2 3 4 5 6 7 8 9 10
1) Set the dip-switches as indicated; in this way the "manual search for distance C" is selected.
2) Press the keys "OPEN" or "CLOSE" to open or close the gate/door until it reaches the point wanted.
3) Movement can also be accelerated by pressing the "<<>>" key.
4) When the gate/door has reached the point wanted the distance has been measured so you can then proceed to
memorisation.
With this procedure the closing point required has been measured and memorised.
1 2
USE AS FOR AN "RO1024" SLIDING GATE
1 2
USE AS FOR A "CR2040" SECTIONAL OR SLIDING DOOR
1 2
1 2
English
25