SubDrive/MonoDrive
Mount the drive as close
as possible to the service
entrance panel.
Special Considerations for Outdoor Use
The controller is suitable for outdoor use with a NEMA 3R rating; however, the following
considerations should be made when installing the controller outdoors:
•
The unit MUST be mounted vertically with the wiring end oriented downward, and
the cover must be properly secured (also applies to indoor installations).
•
The controller shall be mounted on a surface or back plate no smaller than the
outer dimensions of the controller enclosure.
•
NEMA 3R enclosures are capable of withstanding downward-directed rain only.
The controller should be protected from hose-directed or sprayed water as well as
blowing rain. Failure to do so may result in controller failure.
•
The controller should NOT be placed in direct sunlight or other locations subject to
extreme temperatures or humidity.
14
Service Entrance
Panel
Use a dedicated branch circuit for the drive.
Wire directly from the service entrance panel.
Listed fuse/Listed circuit breaker "See Table 1
on page 18 for fuse and circuit breaker sizing."
Service entrance ground rod
Service Entrance
Panel
Mount drive to a sturdy
supporting structure (wall or back plate).
6"
15 cm
6"
15 cm
6"
15 cm
GND
MOTOR OVERLOAD PROTECTION NOTE:
The drive electronics provide motor overload
protection by preventing motor current from exceeding
the maximum Service Factor Amps (SFA). Motor
overtemperature sensing is not provided by the drive.
Wire directly to the service
entrance panel.
DO NOT wire to a sub panel
located in a home.
IN HOME
Sub Panel
GND
Allow a 6" (15 cm) clearance
around the drive for cooling.
Use the holes and
6"
15 cm
guides provided.
(DO NOT drill holes
in the drive.)
GND
GND