Before it is put into service, the system must
be tested to check the operating conditions
of every single component and identify any
malfunctions. In this stage, it is important to
check that all health and safety requirements
have been complied with in full.
To test the system, make the following checks:
Turn on the gas supply tap and check that the
1)
connections are right.;
Check that the mains gas is the same as that
2)
used for commissioning of the appliance, and
carry out the conversion procedure if necessa-
ry (see page 9).
Check that the hob burner is igniting correctly
3)
and his combustion.
Importante
Important
Before making any type of adjustment, acti-
vate all the safety devices provided and deci-
de whether staff at work and those in the vi-
cinity should be informed. In particular, turn
off the gas supply tap and prevent access to
all devices which might cause unexpected
health and safety hazards if turned on.
GB
Important
Importante
Before making this adjustment, check that
the gas supply pressure is the same as the ra-
ted pressure for the type of gas in use (see ta-
ble at back of manual).
To carry out this operation, proceed as follows.
Turn off the gas supply tap.
1)
Pull off the knob (A).
2)
Undo the screws (C) and remove the control
3)
panel (B).
3319960_inst_GB_rev.1

TESTING OF THE APPLIANCE

ADJUSTMENTS
INSTRUCTIONS AND WARNINGS FOR ADJUSTMENT

ADJUSTING GAS CONTROL VALVE MINIMUM SETTING

Check the gas pressure and fl ow-rate at
4)
minimum and maximum settings and adjust if
necessary (see page 6).
Check that the safety thermocouple is working
5)
correctly.
Check that there are no gas leaks.
6)
Check that the nameplates specify the correct
7)
gas for the country of use.
After testing, if necessary instruct the user in all
the skills necessary for putting the appliance
into operation in conditions of safety, in accor-
dance with legal requirements.
Importante
Important
This adjustment is only required if the type
of gas to be connected is diff erent from that
used for testing after the conversion proce-
dure has been carried out ( see page 18).
Caution - Warning
Adjustments must be carried out by author-
ised, qualifi ed staff , in accordance with the
relevant legal requirements.
A
B
- 10 -
C
C
D
ENGLISH