Location - Generac 7 kW NG, 8 kW LP, single-cylinder GH-410 Engine Manual Del Propietário

Ocultar thumbs Ver también para 7 kW NG, 8 kW LP, single-cylinder GH-410 Engine:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

General Information
3.
Close the roof.
4.
Reverse the procedure to convert back to natural gas.
Figure 1.7 - 13, 14, 16, 17, & 20kW,
GT-990/GT-999 (Airbox Cover Removed)
Fuel Selection Lever - "In" Position for Natural Gas Fuel
Figure 1.8 - 13, 14, 16, 17, & 20kW,
GT-990/GT-999 (Airbox Cover Removed)
Fuel Selection Lever - "Out" Position for Liquid Propane
(Vapor) Fuel

1.11 LOCATION

The engine exhaust fumes contain carbon
monoxide, which can be DEADLY. This dan-
gerous gas, if breathed in sufficient con-
centrations, can cause unconsciousness or
even death. This generator must be installed
properly, in strict compliance with applicable
codes and standards. Following installation,
do nothing that might render the system
unsafe or in noncompliance with such codes
and standards.
Operate the generator outdoors ONLY.
10
• Keep exhaust gases from entering a confined
area through windows, doors, ventilation, crawl
spaces or other openings (Figure 1.9).
• It is highly recommended that carbon monox-
ide detector(s) be installed indoors according
to the manufacturer's instructions/recommen-
dations.
• The generator must me mounted safely per
applicable codes and the manufacturer's speci-
fications. Do NOT alter or add to the exhaust
system, or do anything that might render the
exhaust system unsafe or in noncompliance
with applicable codes and standards.
1.11.1
GENERATOR
Install the generator set, in its protective enclosure, outdoors,
where adequate cooling and ventilating air is always available
(Figure 1.9). Consider these factors:
The installation of the generator
NFPA 37, NFPA 54, NFPA 58, and NFPA 70 standards.
Install the unit where air inlet and outlet openings will not
become obstructed by leaves, grass, snow, etc.. If prevailing
winds will cause blowing or drifting, consider using a wind-
break to protect the unit.
Install the generator on high ground where water levels will not
rise and endanger it.
Allow sufficient room on all sides of the generator for mainte-
nance and servicing. This unit must be installed in accordance
with current applicable NFPA 37 and NFPA 70 standards; as
well as any other federal, state and local codes for minimum
distances from other structures. DO NOT install under wooden
decks or structures unless there is at least four (4) feet of clear-
ance above the generator, three (3) feet of clearance on sides
and front, and 18 inches of clearance at back of unit.
Install the unit where rain gutter down spouts, roof run-off,
landscape irrigation, water sprinklers or sump pump discharge
does not flood the unit or spray the enclosure, including any air
inlet or outlet openings.
Install the unit where services will not be affected or obstructed,
including concealed, underground or covered services such as
electrical, fuel, phone, air conditioning or irrigation.
Where strong prevailing winds blow from one direction, face the
generator air inlet openings to the prevailing winds.
Install the generator as close as possible to the fuel supply, to
reduce the length of piping.
Install the generator as close as possible to the transfer switch.
REMEMBER THAT LAWS OR CODES MAY REGULATE THE
DISTANCE AND LOCATION.
The genset must be installed on a level surface. The base frame
must be level within two (2) inches all around.
must comply strictly with