6.2.2
Device 292 A (150 kW)
Proceed as follows to disconnect the internal connection between the filters and PE:
1. The bridge 0 that connects the filter with the protective earth can be found at the
indicated position.
2. Loosen both screws 1 (do not remove them).
3. Fold bridge 0 90° clockwise.
4. Tighten both screws 0.
– Starting torque: 3.4 Nm (30 lb−in)
6.2.3
Devices in the range 366 ... 460 A (190 ... 240 kW)
If devices of this size are to be used in IT systems, factory−set measures have to be taken.
Please consider this when ordering.
EDK94SH366 DE/EN/FR/ES/IT 7.0
Wiring the device
Earthing of internal System 9400 EMC filters
Device 292 A (150 kW)
l
6
94ITSW8002
101