Lenze L-force Drives 9400 E94BSHE Serie Manual De Instrucciones página 109

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Motor temperature monitoring
Terminal X106
T1 T2
SSP94KL0X8
Terminal data
flexible
with wire end ferrule
Motor brake control (optional)
)
Note!
The motor holding brake cannot be released without mains or DC−bus voltage.
Terminal X107
SSP94X6107
Terminal data
flexible
with wire end ferrule
Stripping length or contact length: 8 mm
EDK94SH366 DE/EN/FR/ES/IT 7.0
Devices in the range 145 ... 245 A (75 ... 130 kW)
Labelling
Description
T1
Motor temperature monitoring with PTC element (type−A sensor,
switching performance according to EN 60947−8 for type−A tripping units)
T2
or thermostat (NC contact).
"
Shield connection
Max. conductor cross−section
2
[mm
]
[AWG]
2.5
12
Labelling
Description
Connection of the motor holding brake
BD1
+ (Lenze: WH)
BD2
− (Lenze: BN)
E94AZHx0101: 24 V DC, max. 5.0 A
Observe correct polarity!
+ / −
Supply voltage for the motor holding brake (18 ... 30 V DC)
Observe correct polarity!
Max. conductor cross−section
2
[mm
]
[AWG]
2.5
12
l
Wiring the device
Power terminals
Tightening torque
[Nm]
[lb−in]
0.5 ... 0.6
4.5 ... 5.3
Tightening torque
[Nm]
[lb−in]
0.5 ... 0.6
4.5 ... 5.3
6
!
Slot
0.6 x 3.5
!
Slot
0.6 x 3.5
109

Publicidad

Tabla de contenido
loading

Tabla de contenido