Lenze L-force Drives 9400 E94BSHE Serie Manual De Instrucciones página 120

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

6
Wiring the device
Power terminals
Devices in the range 366 ... 460 A (190 ... 240 kW)
Mains
Terminal X100
L1 L2 L3
A
A
)
Note!
For mounting the cables, you need an extra large spanner socket.
Terminal data
U, V, W, flexible
+
DC bus and external brake resistor
Terminal X104.1/X104.2 Labelling
A
A
A
Terminal data
flexible
120
Labelling
Description
L1
Connection of the phases L1, L2, L3 with ring cable lug for M16 (0).
L2
L3
+
Connection for the PE conductor on the supply side with ring cable
lug for M10 (0).
A
SSP94KL0X9
Max. conductor cross−section
2
[mm
]
[AWG]
300
600 mcm
150
300 mcm
Description
+UG/Rb1
Connection of DC−bus voltage and external brake resistor with ring
cable lug M10 (0).
−UG
In case of double assignment, use sleeve 1from the scope of supply.
Rb2
B
SSP94KL8x
Max. conductor cross−section
2
[mm
]
[AWG]
2 x 240
2 x 500 mcm
l
Tightening torque
[Nm]
[lb−in]
35
315
20
180
Tightening torque
[Nm]
[lb−in]
56
500
EDK94SH366 DE/EN/FR/ES/IT 7.0
!
SW24
SW17
!
Inbus 10 or