KPS-PA50 MINI • Digital clamp meter
contact the circuit. This is normal because the meter is highly sensitive. When
the test leads contact the circuit, the true reading will be shown.
AC Voltage
Range
660mV
6,6V
66V
600V
- Input impedance: 10MΩ
- Overload protection: 660mV range: 250V DC or rms AC, 66V-600V ranges:
600V DC or 600V rms AC.
- Max. input voltage: 600V rms AC
- Frequency range: 40 to 400Hz
- Response: true root mean square value
Note:
At small voltage range, unsteady readings will appear before the test leads
contact the circuit. This is normal because the meter is highly sensitive. When
the test leads contact the circuit, the true reading will be shown..
Frequency
• By A range ( from current clamp):
Range
660Hz
1kHz
>1kHz
- Measurement range: 10 ~ 1kHz
- Input current range: ≥1A rms AC (higher input current at higher frequency)
- Max. Input current: 600A rms AC
• By V range:
Resolution
0,1mV
0,001V
0,01V
0,1V
Resolution
0,1mV
0,001V
0,01V
Accuracy
(1,5% of reading + 10 digits)
(1,2% of reading + 5 digits)
(1,5% of reading + 10 digits)
Accuracy
±(1,5% of reading + 5 digits)
Take it only as referance
35