Technical Specifications
Actuators
Drive torque
Damper area
Running time
Power supply
Frequency
Power
consumption:
- operating
- at end stops
For wire sizing
Weight
Control signals
Position
indication
Angle of rotation:
- Working range
- Limiting
Auxiliary switch
rating
Service life
Sound power
level
Protection class
Degree of
protection
Temperature:
operating/store
Humidity
Maintenance
Standards
This document is subject to change without notice
DAS1
DA1
8 Nm
16 Nm
2
1.5 m
3.0 m
30 s
80 s
Indipendent of load, at nominal conditions and room temperature
AC 24 V ±20% / DC ±10%
50-60 Hz
2.5 W
0.5 W
5.0 VA / 2 A @ 2ms
1.1 kg
ON/OFF and Floating
Mechanical / Potentiometer
90° (93° mech.)
5°...85° in 5° steps
3 (1.5) A, AC 230 V
60'000 cycles
45 dB (A)
II
IP 54 (with cable glands, cable downwards)
-20°...+50°C / -30°...+60°C
5...95% RH (not condensing).
Maintenance-free
89/336 EEC: EN 61000-6-2, EN 61000-6-3
72/23 EEC: EN 60730
DAL1
24 Nm
2
2
4.5 m
1.5 m
125 s
DAS2
DA2
8 Nm
16 Nm
2
2
3.0 m
30 s
80 s
AC 230 V ±15%
50-60 Hz
3.0 W
0.5 W
3.6 VA / 0.1 A @ 2ms
1.2 kg
DAS / DA / DAL
DAL2
24 Nm
2
4.5 m
125 s
5