Technical Specifications

Actuators
Drive Torque
Damper Area
Running Time
Power supply
Frequency
Power
Consumption:
- operating 2.5 W
- at end stops 0.3 W
For wire sizing
Weight
Control Signals:
Position Signal
Angle of Rotation:
- Working Range 90° (93° mech.)
- Limiting 5°...85° in 5° steps
Auxiliary Switch
Rating
Sound Power Level 45 dB (A)
Protection Class
Degree of
Protection
Temperature:
Operating / Store
Humidity
Maintenance
Standards
This document is subject to change without notice
DMS1.1
8 Nm
2
1.5 m
30 s
Indipendent of load, at nominal conditions and room
AC 24 V ±20% / DC ±10%
50-60 Hz
6.0 VA / 3.6 A @ 2ms
1.1 kg
Y1 DC 0...10 V / Ri > 250 K
Y2 0...20 mA / Ri 388
U DC 0...10 V / R > 50 K
3 (1.5) A, AC 230 V
II
IP 54 (with cable glands, cable downwards)
-20°...+50°C / -30°...+60°C
5...95% RH (not condensing).
Maintenance-free
89/336 EEC:
72/23 EEC:
DMS1.1 / DM1.1 / DML1.1 Proportional Actuators
DM1.1
16 Nm
2
3.0 m
80 s
temperature
EN 61000-6-2, EN 61000-6-3
EN 60730
DML1.1
24 Nm
2
4.5 m
125 s
5