Ordering Codes
Codes
Descriptions
DMxx1.1
Actuator AC/DC 24 V
DMxx1.1.S
Actuator AC/DC 24 V with 2 auxiliary switches

Technical Specifications

Actuators
Drive torque
Damper area
Running time
Power supply
Frequency
Power consumption:
- operating 2.5 W
- at end stops 0.3 W
For wire sizing
Control signals
Position Signal U DC 0...10 V / R > 50 KΩ
Angle of rotation:
- Working range 90° (93° mech.)
- Limiting 5°...85° in 5° steps
Auxiliary switch rating
Service life
Sound power level
Protection class
Degree of protection
Temperature: operating/store
Humidity
Weight
Maintenance
Compliance
IS_DMS1.1(S) / DM1.1(S) / DML1.1(S) / DMG1.1(S)_14-88360-1890_Rev. D_11 2010
DMS1.1(S)
8 Nm
1.5 m
2
30 s
Indipendent of load, at nominal conditions and room temperature
AC 24 V ±20% / DC ±10%
50-60 Hz
6.0 VA / 3.6 A @ 2ms
Y1 DC 0...10 V / Ri > 250 KΩ
Y2 0...20 mA / Ri 388 Ω
3 (1.5) A, AC 230 V
60'000 cycles
45 dB (A)
II
IP 54 (with cable glands, cable downwards)
-20°...+50 °C / -30°...+60 °C
5...95% RH (not condensing)
1.1 kg
Maintenance-free
Johnson Controls, Inc., declares that these products are in compliance
with the essential requirements and other relevant provisions of the
EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC
DM1.1(S)
16 Nm
3.0 m
2
80 s
This document is subject to change without notice
DML1.1(S)
DMG1.1(S)
24 Nm
4.5 m
2
125 s
32 Nm
6 m
2
200 s
2