Bosch Praesideo 3.5 Manual De Uso E Instalación página 71

Sistema de megafonía y sistema acústico de emergencia
Tabla de contenido

Publicidad

Praesideo 3.5 | Installation and User Instructions | ISO7240-16: 2007
Excluded clauses
Clause / Requirement
EN54-16, clause 12. 1 Emergency microphone - option with
requirements.
c
Where a pre-announcement attention drawing signal is provided,
an indicator adjacent to the microphone shall show when the sig-
nal has finished and live speech can commence.
Clause / Requirement
EN54-16, clause 13.4. 1 Electrical and other design requirements
The processing of signals shall give the highest priority to the voice alarm condition.
EN54-16, clause 13. 1 3 Message store(s)
Pre-recorded messages shall be stored in non-volatile memory that retains the
messages when all power sources are removed.
NOTE The use of tapes or magnetic or optical data disks for the storage of emer-
gency messages is not acceptable at the time of drafting this European Standard
(see Annex C)
Bosch Security Systems | 2011-02
Compliance
This clause is not part of ISO7240-16.
Compliance
This clause is not part of ISO7240-16.
The NOTE is not part of ISO7240-16.