Descargar Imprimir esta página

Lmo Equipment - Lamborghini Caloreclima ECO 15 Manual Para La Instalación Y El Mantenimiento

Quemadores para gasóleo

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

START-UP
-
Reset by acting on the push-button (20).
-
Power up by turning the main switch to ON. After the pre-ignition time has elapsed the burner starts
running and stays on until the temperature set on one of the control devices causes the latter to trip
(boiler thermostat, room thermostat etc.).
During routine operation the burner only shuts down when a control device is tripped.
-
Adjust the flame by acting on both the air flow via the screw (13) and relative crown (12) and on
forward-rearward excursion of the nozzle holder (10). To adjust the latter act on the screw (17).
-
It is recommended that you bring the holder forward (+) for high or near-maximum flow-rates and shift
it back (-) for low flow-rates (see fig. 8).
N.B. If the burner fails to start up check that the pump has been primed: if it has not, act manually by
undoing the gauge attachment screw (27) and then screwing it back in as soon as you notice fuel exiting the
hole.

LMO EQUIPMENT

The release pushbutton on the equipment is the main component for accessing all the diagnostic functions
(activation and deactivation) as well as for releasing the control and checking device.
The release pushbutton has a multicoloured led which indicates the state of the control and checking device
during operation and when the diagnostic function is in use.
Condition
Standby, other intermediate states
Fuel preheating "on", waiting time 5s.max
Ignition stage
Correct operation
Incorrect operation, current level of
flame detector below permitted minimum
Drop in voltage
Burner lock out
Fault (see table on page 8)
Stray light before burner ignition
Rapid flashing for diagnostics
If the burner is locked out, there will be a steady red light on the lock out pushbutton.
By pressing the transparent pushbutton, the control and checking device will be released.
By pressing it for more than 3 seconds, the diagnosis stage will be activated (red light flashes rapidly). The
table below describes the causes of the lock out or fault in relation to the number of flashes (always red).
The diagnosis function is interrupted by pressing the release button for at least 3 seconds.
EQUIPMENT STATE INDICATORS
Description
Colour sequence
No light
Yellow
Yellow, flashing
Green
Green, flashing
Alternating yellow red
Red
Red, flashing
Alternating green red
Red, rapid flashing
38