Sime Brava Slim 40 BF Manual De Instalación Y Mantenimiento página 84

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Split pipe system
The split pipe system is supplied with the combustion air inlet
diaphragm which is to be mounted, after the sections have been
eliminated according to the total load loss which is calculated
by summing the load losses of the inlet ducts to those of the
outlet ducts.
2
1
KEY:
Split pipe system with take-off point
1
Inlet diaphragm
2
Air inlet
3
Smoke outlet
4
Take-off point for smoke analysis
5
Load loss accessory Ø 80 mm
Description
90° curve MF
45° curve MF
Horizontal extension W. 1000
mm
Vertical extension W. 1000 mm
Wall terminal
Condensate recovery Tee
Roof outlet terminal (*)
(*) The losses of the roof outlet terminal at inlet include the
manifold code 8091400.
for the boiler to operate correctly it is necessary that a
NOTE:
minimum distance of 0.50 m of the duct is respected with a 90°
inlet curve.
Example: calculation of the load loss of a Brava Slim 40 BF boiler.
Accessories Ø 80
Code
mm
Extension W. 1000
8077309
mm (horizontal)
Extension W. 1000
8077309
mm (horizontal)
90° curve
8077410
90° curve
8077410
Wall terminal
8089501
TOTAL
84
3
4
5
Fig. 15
Load loss (mm H
Code
Brava Slim 40 BF
Inlet
Outlet
8077410
0,70
1,50
8077411
0,60
1,00
8077309
0,40
0,65
8077309
0,30
0,30
8089501
0,25
2,00
8093300
-
2,20
8091200
4,00
0,40
Load loss (mm H
O)
2
Quantity
Inlet
Outlet
Total
4
4 x 0,40
-
1,60
4
-
4 x 0,65
2,60
2
2 x 0,70
-
1,40
2
-
2 x 1,50
3,00
2
0,25
2,00
2,25
10,85
(installation permitted since the total of the load loss of the
accessories used is less than 15,0 mm H
With this total load loss, sections 1 to 8 (inclusive) must be
removed from the inlet diaphragm (2).
2
No. of sections to be removed
1 ÷ 2
1 ÷ 4
1 ÷ 5
1 ÷ 6
1 ÷ 7
1 ÷ 8
1 ÷ 10
O)
Entire diaphragm
2
(*) Maximum load loss permitted.
Description
K (mm)
W (mm)
O).
2
Total load loss (mm H
Brava Slim 40 BF
0 ÷ 2,0
2,0 ÷ 4,0
4,0 ÷ 6,0
6,0 ÷ 8,0
8,0 ÷ 9,0
9,0 ÷ 11,0
11,0 ÷ 13,0
13,0 ÷
15,0
(*)
L
K
120
Brava Slim 40 BF
245
450
EN
Fig. 16
O)
2
Fig. 17

Publicidad

Tabla de contenido
loading

Tabla de contenido