– press the button
>
and select "1" (LPG)
Procedure which MUST be carried out after:
– the nozzles for gas conversion
– changing the gas valve following a fault
– changing the the electronic board following a fault
– electrode
– fan
– burner
– go into the parameter section (if not already there) by pressing
the buttons
r
and
t
(for approximately 5 seconds) at the
same time until "PAR 01" (parameter number) and the value
set (0-4) appears on the display
– keep the button
t
pressed and scroll through the parameters
until reaching parameter "PAR 49"
– press and hold the button
>
– the modified value will be stored automatically
– keep the button
t
pressed and scroll through the parameters
until reaching parameter "PAR 70"
– press the button
>
to set the value at "5"
– the modified value will be stored automatically
to set the value at "49"
– exit the parameter section by pressing and holding down the
buttons
r
and
t
at the same time
until the delivery temperature is displayed.
m
IMPORTANT
To complete this task the user MUST carry out the
following procedure.
Adjusting maximum gas pressure:
– press the button
y
until "SUMMER" mode
selected
– press button
r
and set the DOMESTIC HOT WATER SET to
maximum using the button
– press and hold down the buttons
for approximately 6 seconds until the message "Au" appears
on the display alternating with "to"
– open one or more than one hot water tap
– the boiler will start up and the message "P01" will appear on
the display (Adjusting maximum gas pressure)
– press the buttons
>
or
<
until the pressure value indicated in
the table appears on the pressure gauge
– once the value indicated in the table has been reached, press
the button
y
for approximately 2 seconds to confirm the
value which will then flash once.
Adjusting minimum gas pressure:
– press the button
r
twice, the message "P00" will appear on
the display
– press the buttons
>
or
<
until the pressure value indicated in
the table appears on the pressure gauge
– once the value indicated in the table has been reached, press
the button
y
for approximately 2 seconds to confirm the
value which will then flash once
(approximately 5 seconds)
l
has been
>
and
at the same time
>
y