EN
4.5
Unscheduled maintenance
If replacing the electronic board , the user MUST set the
parameters as indicated in the table.
Type
No.
Description
Index showing boiler power in kW
PAR
01
2 = 40
Hydraulic configuration
0 = rapid
1 = storage tank with thermostat or
PAR
02
heating only
2 = hot water tank with sensor
3 = bithermic
4=instant with solar power input
Gas Type Configuration
PAR
03
0 = G20; 1 = LPG
Combustion configuration
0 = sealed chamber with combustion
control
PAR
04
1 = open chamber with smoke
thermostat
2 = Low NOx
To enter "Parameter setting and display"refer to the indications
provided in the specific section.
Once the parameters in the table have been set, you must carry
out the "Automatic calibration procedure".
If the gas valve and/or the ignition/detection electrode and/or the
are replaced, the user must still carry out the entire phase
fan
of "Automatic calibration procedure" described in the specific
section.
4.6
Malfunction codes and possible solutions
LIST OF MALFUNCTION/FAULT ALARMS
Type
No.
Fault
ALL
01
Smoke thermostat
Low water pressure
ALL
02
in system
High water pressure
ALL
03
in system
Domestic hot water
sensor fault (return
ALL
04
sensor fault for T
models)
ALL
05
Delivery sensor fault
ALL
06
No flame detection
Sensor or safety
ALL
07
thermostat
intervenes
Fault in the flame
ALL
08
detection circuit
Setting
2
0
0 or 1
0
Solution
- Contact the Technical
Assistance Centre
- Restore pressure
- Check for any leaks in the
system
- Empty the system via the
drain valve on the hydraulic
assembly and bring the
pressure to approximately
1.2 bar
- Check connections
- Check the sensor is working
- Check connections
- Check the sensor is working
- Check the integrity of the
electrode and check that it is
not grounded
- Check gas availability and
pressure
- Check the integrity of the gas
valve and the card
- Check the sensor or
thermostat connections
- Deaerate the system
- Check the bleed valve
- Replace the sensor or the
thermostat
- Check that the pump impeller
is not blocked
- Check the integrity of the
electrode and check that it is
not grounded
- Check the integrity of the gas
valve and the card
Type
No.
Fault
No water circulating
ALL
09
in the system
Auxiliary sensor
ALL
10
fault
Gas valve modulator
ALL
11
disconnected
Domestic hot water
ALL
12
sensor fault in tank
mode
Smoke probe
ALL
13
intervention
ALL
14
Smoke probe fault
Fan check cable
ALL
15
disconnected
Condensate level
ALL
18
fault
Maximum number
ALL
28
of consecutive
resets reached
Return sensor fault
ALL
30
(boiler sensor fault
for T models)
Fault due to low
ALL
37
network voltage
Incorrect network
ALL
40
frequency detected
Flame loss more
ALL
41
than 6 consecutive
times
ALL
42
Button fault
Open Therm
ALL
43
communication fault
Gas valve timeout
ALL
44
fault without flame
Lock for ∆T delivery/
ALL
56
return over max
limit (open vent)
Lock for flow
ALL
57
temperature (FT)
check (open vent)
Self-calibrating
ALL
62
procedure is
required
Incorrect positioning
ALL
72
of the delivery
sensor
Second delivery
ALL
74
sensor fault
EV2 SGV current
ALL
77
max/min absolute
limits error
Solution
- Check the rotation of the
pump rotor
- Check the electrical
connections
- Replace the pump
- Check PAR 02 "hydraulic
configuration"
- Check the electrical
connection
- Check the electrical
connection
- Set the parameter PAR 04
(Combustion configuration)
to 0
- Check the sensor is working
- Replace the smoke probe
- Replace the smoke probe
- Check the electrical
connection of the smoke
probe
- Contact the Technical
Assistance Centre
- Check the connection cable
between the fan and the board
- Check for any clogging in
the pipe which takes the
condensate to the siphon
- Check that the siphon is not
clogged
- Wait 1 hour and try unblocking
the board again
- Contact the Technical
Assistance Centre
- Replace the return probe
- Check parameters
- Contact the Technical
Assistance Centre
- Check the voltage
- Contact your network provider
- Contact your network provider
- Check the ignition/detection
electrode
- Check the gas supply (open
valve)
- Check mains gas pressure
- Check that buttons are
working
- Check the OT electric
connection
- Check gas valve and board
- Contact the Technical
Assistance Centre
- Contact the Technical
Assistance Centre
- Carry out the self-calibrating
procedure (see the specific
section)
- Check delivery sensor
operation and position
- Check second delivery sensor
operation and position
- Check gas valve and board
101