AERMEC VMF-RCC Manual Del Usuario página 92

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Regulation and Control Service
Project
VMF-RCC panel
Subject
Electronic adjustment
Document
E5 panel technical specifications
Edition
1
Date
G
ENERATOR HOT SET PAGE
Use this page to:
 edit the chiller water output set during winter functioning. The acceptable values range
from 30.0 to 70.0 [°C]. Level: user.
 edit the parameter that identifies the band of values in which the chiller water output set
can vary during winter functioning if the Economy environment control has been enabled.
The acceptable values range from 3.0 to 20.0 [°C]. Level: user.
To enter the language editing mode, press the
is displayed. To change the value, act on the increase (
is confirmed by pressing the enter (
highlighted by the disappearance of the denied display.
Press the ESC key for the system to display the menu page.
Using the Page Up and Page Down keys, scroll the pages contained in the sub-menu.
92
2104_2696105_00
File
09/08/2017
Author
) key, while the effective memorisation in eeprom is
SpecificheTecnicheVMF_RCC(Ed0)_EN.doc
F. Carpanese
key. This status is highlighted when no string
) and decrease (
Page 40/61
Code
Group
Code
Type
indoor
) keys. The data

Publicidad

Tabla de contenido
loading

Tabla de contenido