Subject
Electronic adjustment
Document
E5 panel technical specifications
Edition
1
Date
To enter the data editing mode, press the
displayed. To change the value, act on the increase (
confirmed by pressing the enter (
highlighted by the disappearance of the denied display.
Press the ESC key for the system to display the menu page.
Using the Page Up and Page Down keys, scroll the pages contained in the sub-menu.
C
LIMATE PAGE FOR GENERATOR SET POINT
The compensation curve of the water output set point of the chiller can be set on this page,
according to the external air temperature. Level: user.
Reference season of
the compensation curve
Tua2
TWout [°C]
Tua1
Tae1
09/08/2017
Enabling
compensation
Tae2
Figure 1: Example of compensation curve according to the external air temperature
Author
F. Carpanese
key. This status is highlighted when no data is
) and decrease (
) key, while the effective memorisation in eeprom is
TWout [°C]
Tua1
Tua2
TAext [°C]
Group
Code
Type
indoor
) keys. The data is
(Tae1, Tua1)
(Tae2, Tua2)
Page change to
select the
season
Tae1
Tae2
2104_2696105_00
TAext [°C]