Evaporative Cooling System
In the event it is discovered that a pump is not operational or supplying water to the system, the H2
Evaporative system is equipped with an Emergency Operation override.
Before taking any measures please follow steps below:
1. Ensure system has and is receiving water.
2. Ensure pump is receiving power (and Strainer Basket is not clogged for jet systems)
3. Ensure Filter is not clogged and preventing water from passing.
If the above steps have been completed and it is determined that there is a problem with the recirculation of water
from the trough to the spray bar (pump, filter, cracked line, etc...) then follow below procedure to operate the
system in emergency state.
1. Disconnect the incoming water line for the brass fitting on the float tank
2. Attach incoming water line to brass fitting on feed pipe (Extra hose may be required)
3. Close 1 ½" Ball Valve above filter and turn on water supply from the hose.
4. The length of the system determines the amount of water that will be distributed to the Evaporative
Media.
! THIS IS NOT A PERMANENT SOLUTION AND SHOULD ONLY BE
USED WHILE A PERMANENT SOLUTION IN BEING IMPLEMENTED!
Hog Slat Inc. Newton Grove, NC USA November 2018

Emergency Operation

32