The IS 3360, IS 3360 MX, IS 345, IS 345 MX and IS 3180 are certified under IEC
62386-103 as single-master application controllers. This means that their DALI 2
certification only covers applications in which only DALI control gears are connected
to the DALI bus. We furthermore guarantee that the presence detectors are also suit-
able for use in multi-master applications with selected DALI sensors for extending the
detection zone. For further information in this regard, please refer to the Master/Slave
section. At this points we expressly point out that no DALI-2 certification is available
for using the product in a DALI bus system with several control devices.
Note: when connecting DALI-2 input devices for extending the detection zone, please
pay attention to the power consumption of individual sensors so as to make sure that
the maximum available current is not exceeded.
5� Mounting
• Check all components for damage.
• Do not use the product if it is damaged.
• Select an appropriate mounting location, taking the reach and motion detection into
consideration.
Procedure for installing concealed power supply lead (Fig� 5�1)
Procedure for installing surface-mounted power supply lead (Fig� 5�2)
IS 3360, IS 3360 MX Highbay, IS 345, IS 345 Highbay
Procedure for installing concealed power supply lead (wall mounting) IS 3180
(Fig� 5�3)
• Switch OFF power supply�
• Detach designer trim from sensor module.
• Disconnect sensor module from the load module.
• Connect to mains power supply.
– Surface-mounted power supply lead (Fig� 5�4)
– Concealed power supply lead (Fig� 5�5)
• Insert fastening screws and mount load module.
Limiting reach
The detection zone can be optimised to suit requirements.
– By adjusting the lens. (Fig� 5�8 / 5�10)
– By using the half-round clip-on shroud. (Fig� 5�11)
Note: to limit reach, the sensor module must be detached from the load module.
• To set the required reach, undo the screws or completely remove them.
• Move lens into required zone.
• The half-round clip-on shroud provided can be used for masking out any number of
lens segments to shorten reach as required.
• Afterwards, fix the lens in place with the screws.
28
Detection zone / reach
IS 3360 (Fig� 5�6)
IS 345 (Fig� 5�8)
IS 3360 MX (Fig� 5�7)
IS 345 MX (Fig� 5�9)
Mounting height
Mounting height
Reach
14 m
10 m
9 m
14 m
6 m
16 m
2.8 m
18 m
IS 3180 (Fig� 5�10)
Mounting
20 m lens
height
Setting level tangential
1.5 m
8
5 m
–
6 m
–
7 m
–
8 m
20
12 m
2.0 m
8
5 m
–
6 m
–
7 m
–
10 m
20
20 m
2.5 m
8
6 m
–
8 m
–
10 m
–
13 m
20
20 m
3.0 m
8
8 m
–
9 m
–
12 m
–
17 m
20
20 m
Note: the factory setting is 20 metres
• Fit sensor and load module together and screw into place.
• Switch ON power supply�
• Set functions. (➔ "6� Funtion")
• Fit designer trim.
6� Function / operation
Factory settings
Twilight setting:
daytime mode
Time setting:
5 s
Main light:
80%
Reach
14 m
30 m × 4
10 m
25 m × 4
8 m
20 m × 4
6 m
15 m × 4
4 m
10 m × 4
8 m lens
radial
Setting level tangential
radial
2.5 m
4
3 m
2.5 m
–
5 m
3.0 m
–
6 m
3.0 m
–
7 m
4.5 m
8
9 m
2.5 m
4
4 m
3.0 m
–
5 m
3.5 m
–
6 m
4.0 m
–
8 m
4.5 m
8
8 m
3.0 m
4
5 m
4.0 m
–
7 m
5.0 m
–
8 m
5.0 m
–
9 m
4.0 m
8
10 m
4.0 m
4
5 m
4.5 m
–
6 m
5.0 m
–
8 m
4.0 m
–
10 m
4.0 m
8
13 m
29
2.0 m
2.5 m
3.0 m
3.0 m
3.5 m
3.0 m
3.0 m
3.0 m
3.0 m
3.5 m
3.0 m
3.5 m
3.5 m
4.0 m
3.5 m
3.0 m
3.0 m
4.0 m
4.5 m
5.5 m