UL notes
WARNING: Risk of electric shock and fire
If the branch circuit protection device opens, this may indicate interruption of a fault current.
To reduce the risk of a fire or electric shock, current-carrying parts and other components of the
controller must be checked and replaced if they are damaged.
Disregarding these instructions can result in death, serious injuries or damage to equipment.
CAUTION
Use copper leads with a temperature rating of at least 75 °C for use with a low voltage, limited
energy, isolated power supply.
The device is designed for use with a low voltage, limited energy, isolated power supply.
SSCR (single and group installation)
Suitable for use in circuits with a maximum 5 kA rms symmetrical current and ≤ 480 V, with 20
A class RK5 (type 1 coordination) fuses.
Suitable for use in circuits with a maximum 100 kA rms symmetrical current and ≤ 480 V, with
30 A class J or CC (type 1 coordination) fuses.
FLA
3 A (480 V AC), 7.6 A (480 V AC)
Revision 1, dated 01/2021