Defrost starts after a period of time set through "d0" starting from the last defrost cycle.
The inner fan operates according to the value given to parameter F3.
The defrost control is automatically inhibited and the card self-calibration process de-
activated.
Condenser probe error
If the condenser probe is broken or the relevant connection interrupted, the display shows
the label [E2].
The condenser fan keeps operating according to the value given to parameter "F8".
If the room probe is broken, neither the Hyper Cold nor the Energy Saving function can be
activated.
If the three probes are broken or disconnected, E0, E1, and E2 alternate on the display.
If the room temperature exceeds the setpoint, the label [AH] and the
temperature reached alternate on the display. The buzzer sounds.
Press up to display the duration of the event causing the alarm.
The buzzer can be turned off by pressing the key
The visual alarm signal stays on until the temperature returns within the normal range.
If the room temperature is below the setpoint, the label [AL] and the
temperature reached alternate on the display. The buzzer sounds.
Press down to display the duration of the event causing the alarm.
The buzzer can be turned off by pressing the key
The visual alarm signal stays on until the temperature returns within the normal range.
HIGH AND LOW TEMPERATURE ALARMS MEMORIZED
The defrost led blinking at high frequency indicates high or low
temperature alarm.
The temperature reached blinks on the display
The duration of the event causing the alarm, expressed in minutes, blinks
on the display.
The defrost led is reset to standard operation
The display shows [rES] after the abnormal event.
HIGH TEMPERATURE ALARM
LOW TEMPERATURE ALARM
29