Appendix
A.1 How to configure an IP address on
your PC
1. Open "Control Panel".
2. Select "Network and Sharing Center".
3. Click [Change adapter settings].
4. Right-click and select "Properties" for the
Ethernet adapter. Typically "Local Area
Connection".
5. Select properties for "Internet Protocol Version 4
(TCP/IPv4)".
6. Select the "Alternate Configuration" tab and enter
the IP address and subnet mask of your PC.
See fig. 1.
Fig. 1
Example from Windows 7
A.2 Web server configuration
The built-in web server offers easy monitoring of the
CIM 500 module and makes it possible to configure
functions and Industrial Ethernet protocols.
By means of the web server you can also update the
firmware of the CIM 500 module and store/restore
settings.
To connect a PC to the CIM 500, proceed as follows:
1. Connect the PC and the module, using an
Ethernet cable.
2. Configure the Ethernet port of the PC to the
same network as the CIM 500, e.g.
192.168.1.101. See section
an IP address on your
3. Open a standard Internet browser and
type 192.168.1.100 in the URL field.
4. Log in to the web server. See fig.
110
A.1 How to configure
PC.
2
1