NOT I CE ON IN STALLATION .
WARNING
Connecting the wallbox to the power supply other than as specified in this section
can result in incompatibility of the installation as well as the risk of electric shock,
and thus cause damage to the wallbox, and injury or death.
• Only connect the wallbox to a power supply in a configuration that is specified
in this section.

INSTALLATION ADVICE

Ground
Input
MCB
RCD
NOTE
For a TT or IT electric grid with 230 V from line to line, the charging station must be
installed with one phase being connected to clamp L1 and the other phase being
connected to clamp N.
NOTE
Make sure that the provided ground connection meets the local regulations.
The ground loss monitor functionality of the wallbox is limited to physical ground
loss detection and cannot detect quality.
2 4
TN-system
TT-system
IT-system
1-phase
3-phase
Ethernet cable crimper
C-characteristic (MCB must be selected to match the amperage settings
of the charging station, considering MCB manufacturer specifications)
40 A, 30 mA, AC Type A
PE-cable
Earth electrode installed separately
(to be installed)
230 V ± 10 %, 50 Hz
400 V ± 10 %, 50 Hz