WARNING
Not using round cables for installation and
mounting the sealing nuts of the cable glands
incorrectly will affect the protection against
moisture of the wallbox, which can result in
the risk of electric shock.
• Use round cables for installation.
• Make sure that the sealing nuts are mounted
on the outside of the wallbox.
a. Remove the lock nuts from the cable glands
and mount the cable glands on the power
supply cable and (optionally) on the CT coil
cable and Ethernet cable with their sealing
nuts on the outside of the wallbox.
b. Insert the supply cables from the back
of the wallbox through the cable opening
of the main assembly.
c. Make sure the following lengths of cables are
available after the cable glands, then tighten
each cable gland.
• Power supply cable: > 180 mm.
• CT coil cable (optional): > 80 mm.
• Ethernet cable (optional): > 400 mm.
d. Secure the cable glands by tightening
their lock nuts.
2 8
M OUNT MAI N ASSEMBLY ONTO
WALL BRAC K ET.
See the corresponding illustrations
B 5.3
in manual
B.
1. Engage the top edge of the main assembly
with the top of the wall bracket and then
rotate the main assembly so it is flat on the
wall bracket.
2. Mount main assembly.
WARNING
Not mounting all the screws and washers on the
inside of the main assembly when mounting it
onto the wall bracket will affect the protection
against moisture of the wallbox, which can result
in the risk of electric shock.
• Make sure that all screws together with their
corresponding washers are mounted.
While holding the main assembly in place, insert
the four screws M6 x 16 mm together with the
bonded sealing washers 6.6 mm x 11 mm and
fasten them.