aquatermic inverter Manual Del Usuario página 10

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Operation Instructions
Go to the FUNCTION page and locate Ctrl. state, then, configure it through the Up/Down key
.
[Notes]
① If "Remote sensor" is set to "With", "T-out water" and "T-room" are available. While if
"Remote Sensor" is set to "Without", only "T-out water" is selectable.
② This setting will be memorized upon power failure.
2.2.3 Fast Hot Water
When hot water is needed urgently, this function can be configured to be "On", In this case, the
heat pump and the water tank heater will work together to generate sanitary hot water in a quickest
way.
[Operation Instructions]
Go to the FUNCTION page and locate "Fast hot water", then, configure it through the Up/Down
key
, "On" or "Off".
[Notes]
① It works only when "Water tank" is set to "With".
② This setting will be memorized upon power failure.
2.2.4 T-water Ctrl (Water Temperature Control for Heating)
There are two options for the leaving water temperature control, high-temperature water
circulation (High temp) and normal-temperature water circulation (Normal temp). When "Floor
config" is set to "With" (see 2.2.29), then the leaving water temperature control is defaulted to be
"Normal temp". When "FCU config"(see 2.2.31) or "Radia config"(see 2.2.30) is set to"With", the
leaving water temperature can be configured to either "High temp" or "Normal temp".
[Notes]
"Floor config", "FCU config", and "Radia config" all can be configured to be "With". However,
as long as "Floor config" is configure to be "With", only "Normal temp" is available.
[Operation Instructions]
Go to the FUNCTION page and locate "T-water ctrl.", then, configure it through the Up/Down
, "High temp." or "Low temp.".
key
[Notes]
① When this setting is changed, the following parameters will return to the default values.
Water out temperature for heating
Upper limit water-out temperature at the weather-dependent
Lower limit water-out temperature at the weather-dependent
② This setting will be memorized upon power failure.
2.2.5 Cool + Hot water
This compound mode enables the user to give priority to the "Cool" or "Hot water" mode
depending on the actual demand.
[Operation Instructions]
Full Name
mode for heating
mode for heating
Displayed Name
WOT-Heat
Upper WT-Heat
Lower WT-Heat
7
Default
45°C/113°F[High]
35°C/95°F[Normal]
61°C/142°F[High]
35°C/95°F[Normal]
55°C/131°F[High]
29°C/84°F[Normal]

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido