BTL7-A/C/E/G5_ _-M_ _ _ _-B/Z-DEX_-K_ _/KA_ _
Micropulse Transducer - Rod Style
6
Calibration procedure (continued)
6.3.2

Adjusting

The detailed procedure for adjusting is
described on page 19 ff.
The factory-set null point and end point are replaced by a
new start point and end point and the associated output
values can be adjusted. The start and end values can be
adjusted as you like up to the limits.
Steps
► Move magnet to the new start position.
► Read new start point by activating the programming
inputs.
► Set the desired start value by activating the
programming inputs.
New start
value
New null point
Fig. 6-4:
Adjust a new start value
www.balluff.com
► Move magnet to the new end position.
► Read new end point by activating the programming
inputs.
► Set the desired end value by activating the
programming inputs.
New end
value
Before
Fig. 6-5:
Adjust a new end value
after
6.3.3

Reset

Restoring the transducer to its factory settings.
Ignition protection "d"
Flameproof enclosure
New end point
The detailed procedure for the reset is
described on page 21.
english
Before
After
17